To access the full text documents, please follow this link: http://hdl.handle.net/2117/15003

Doubly fed induction generator subject to symmetrical voltage sags
Rolán Blanco, Alejandro; Córcoles López, Felipe; Pedra Durán, Joaquim
Universitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica; Universitat Politècnica de Catalunya. QSE - Qualitat del Subministrament Elèctric
The aim of this paper is to analyze the dynamic behavior of the doubly fed induction generator (DFIG) subject to symmetrical voltage sags caused by three-phase faults. A simple control algorithm is considered and assumed ideal: the rotor current irf in the synchronous reference frame is kept constant. This hypothesis allows the electrical transient to be solved analytically, providing a comprehensive description of DFIG behavior under symmetrical sags. The fault-clearing physics of symmetrical sags is also analyzed. That is, the fault is cleared in the successive natural fault-current zeros, leading to a voltage recovery in one, two, or three steps. This clearing process, called discrete fault clearing in this paper, results in a more accurate sag modeling than the abrupt or instantaneous fault clearing (the usual modeling in the literature). The fault-clearing process has a strong influence on the rotor voltage required to control the rotor current after fault clearing. To compare the effects of both abrupt and discrete sags, different wind turbine (WT) operating points, which determine different generated powers, are considered. This study helps in the understanding of WT fault ride-through capability.
Peer Reviewed
-Àrees temàtiques de la UPC::Energies::Energia elèctrica::Automatització i control de l'energia elèctrica
-Àrees temàtiques de la UPC::Energies::Energia eòlica::Aerogeneradors
-Àrees temàtiques de la UPC::Enginyeria mecànica::Motors::Motors elèctrics
-Induction generators
-Electric machinery, Induction
-Wind power
-Electric power system stability
-Doubly fed induction generator (DFIG)
-fault clearing
-fault ride-through capability
-symmetrical voltage sag
-Motors elèctrics d'inducció
-Energia eòlica
-Energia elèctrica
-Aerogeneradors
-Sistemes elèctrics de potència -- Estabilitat
Article - Published version
Article
         

Show full item record

Related documents

Other documents of the same author

Pedra Durán, Joaquim; Córcoles López, Felipe; Monjo Mur, Lluís; Bogarra Rodríguez, Santiago; Rolán Blanco, Alejandro
Rolán Blanco, Alejandro; Córcoles López, Felipe; Pedra Durán, Joaquim
Rolán Blanco, Alejandro; Pedra Durán, Joaquim; Córcoles López, Felipe
Rolán Blanco, Alejandro; Córcoles López, Felipe; Pedra Durán, Joaquim; Monjo Mur, Lluís; Bogarra Rodríguez, Santiago
Aguilar Galván, Daniel; Vázquez Guzmán, Gerardo; Rolán Blanco, Alejandro; Rocabert Delgado, Joan; Córcoles López, Felipe; Rodríguez Cortés, Pedro
 

Coordination

 

Supporters