Control of DFIG-WT under unbalanced grid voltage conditions

Other authors

Universitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica

Universitat Politècnica de Catalunya. SEER - Sistemes Elèctrics d'Energia Renovable

Universitat Politècnica de Catalunya. QSE - Qualitat del Subministrament Elèctric

Publication date

2009

Abstract

The voltage oriented control in the synchronous reference frame (VOC-SRF) have been extensively used for controlling wind turbines based on doubly fed induction generators (DFIG-WTs) through the rotor side converter of a back to back power processor. Although its performance is fast and accurate under balanced conditions its behaviour is not good enough when the voltage of the mains is unbalanced, unless an independent control for the positive and the negative sequence is implemented. This paper proposes a new control system able to control the DFIG-WT under unbalanced conditions using a simple algorithm, which does not need to be implemented for both symmetrical components but on the static αβ reference frame. The reliability of the presented system will be tested by means of PSCAD simulations under balanced and unbalanced grid conditions.


Peer Reviewed


Postprint (published version)

Document Type

Conference lecture

Language

English

Related items

http://www.ieeexplore.ieee.org/search/srchabstract.jsp?tp=&arnumber=5316125&queryText%3D%28%28Authors%3ALuna%29+AND+Watanabe%29%26openedRefinements%3D*%26matchBoolean%3Dtrue%26searchField%3DSearch+All

Recommended citation

This citation was generated automatically.

Rights

http://creativecommons.org/licenses/by-nc-nd/3.0/es/

Open Access

Attribution-NonCommercial-NoDerivs 3.0 Spain

This item appears in the following Collection(s)

E-prints [72986]