Verification of the dependability of an improved negative-sequence based shunt reactor protection in a power grid with inverter-based resources (IBR)

Otros/as autores/as

Universitat Politècnica de Catalunya. Departament d'Enginyeria Elèctrica

Prieto Araujo, Eduardo

Schulte, Horst

Meiske, Frank

Fecha de publicación

2025-06-27



Resumen

This thesis validates a simplified negative-sequence–based protection scheme for turn-to-turn faults (TTFs) in shunt reactors and benchmarks its dependability in both conventional synchronousmachine grids and inverter-based resource (IBR) environments. A 500 MW transmission test bench—mark connected to a 50 MW offshore wind farm through land/sea cables, and shuntreactor compensation—was modeled. The farm Model was implemented in three different ways: (i) a conventional three-phase voltage source (Model I), (ii) a grid-following inverter (Model II), and (iii) a grid-following inverter with negative-sequence injection (Model III). The protection algorithm measures terminal currents, extracts their negative-sequence component, converts it to per-unit, and issues a trip when a fixed threshold is exceeded. Dependability was assessed for two fault severities (TTF = 1 % and 0.065 %) and two grid strengths (SCR = 10 and 1). Results show that the terminal negative-sequence current |I2|—and hence sensitivity—declines with decreasing SCR, yet remains above the detection threshold for SCR ≥ 0.1. At TTF = 1 %, all models tripped reliably; Model I generated the largest |I2| in every case, while Model III surpassed Model II in weak grids. At TTF = 0.065 %, detection margins narrowed: Model II edged Model III in strong grids, but Model III regained superiority under weak grids despite Moving-Average-Filter limitations. A practical lower-sensitivity bound was identified at TTF ≈ 0.035% for SCR = 5. Parametric sweeps confirmed near-linear |I2| trends versus both TTF %, with Model I exhibiting the steepest gradients. Overall, Model I remains the most robust, Model III is the best IBR solution—approaching Model I in weak grids or at higher fault levels—and Model II is adequate only in strong grids. These findings demonstrate that the proposed algorithm can dependably detect TTFs down to 0.065 % even in inverter-dominated, low-SCR networks and highlight the value of negativesequence injection for future IBR protection strategies.


Outgoing

Tipo de documento

Master thesis

Lengua

Inglés

Publicado por

Universitat Politècnica de Catalunya

Citación recomendada

Esta citación se ha generado automáticamente.

Derechos

Open Access

Este ítem aparece en la(s) siguiente(s) colección(ones)